Remote communications, No set-up for standard modem behavior, Remote communications" o – Honeywell Excell 500/600 Controll System 500-XCL5010 User Manual

Page 43: Ge 43 for, Modem or isdn terminal adapter connections, Modem requirements

Advertising
background image

EXCEL 500/600 INSTALLATION INSTRUCTIONS

REMOTE COMMUNICATIONS

The following applies to the XC5010C and XCL5010, only.
For remote communications with up to three XBS Building
Centrals, a modem or ISDN terminal adapter can be
connected directly to the serial port of the XC5010C CPU
(either front or rear connection) or the serial port of the
XCL5010.

NOTE: Remote communication via modem or ISDN terminal

adapter requires firmware version V2.1.0 or higher.

NOTE: XBSi building supervisors are not supported for

remote communication.

Modem or ISDN Terminal Adapter

Connections

The front serial port of the XC5010C CPU accepts a standard
modem cable with a female 9-pin connector.

Fig. 92. Serial port locations on Excel 500

Use the cable that is supplied with the modem/ISDN terminal
adapter. To connect to the terminals of the rear serial port of
the XC5010C, use cable XW571 (length: 6 ft (1.9m)).

Table 25. XW571 Connection

Pin XC5010C

RS232 signal

Wire color

2

RTS

Blue

3

GND

White

4

TxD

Yellow

5

RxD

Green

6

CTS

Violet

7

DTR

Black

8 (not used)

SG

White

9

DCD

Brown

10

Shield

Clear

11 (not used)

RI

Red

NOTE: Pin numbers shown are for the rear connector of the

XC5010C Computer Module.

The serial port of the XCL5010 CPU accepts a standard
modem cable with a female 9-pin connector.

Fig. 93. Serial port location on Excel 500-XCL5010

Use the cable that is supplied with the modem/ISDN terminal
adapter. The communication speed is 9600 baud by default
but can be set as high as 38.4 Kbaud.

NOTE: See section "Serial Port" on page 32, for signals of

serial port.

Modem Requirements

• Modem must support Hayes compatible command set (not

V150 or V151 = Microsoft command set)

• Modem must support alpha-numeric return codes
• Modem must follow serial baud rate of the CPU
• Modem must support auto-bauding (baud rate fall-back)
• When carrier detect (connect) is reported, the carrier must

be on simultaneously at both modems (on CPU side and
on XBS side) use same modem

• After a switch-ON of the DTR line by the CPU or XBS, the

modem must accept a dial command after 3 seconds

• Modem must answer AT commands in less than 3

seconds

No Set-up for Standard Modem Behavior

If no special modem behavior is required, there is no need to
set up or initialize the modem/ISDN terminal adapter. The
XC5010C/XCL5010 CPU will automatically detect the device
(MMI or modem) attached to the serial port and set the
appropriate communication speed. The controller will also
automatically adapt to alphanumeric return codes used by the
modem. This automatic detection and adjustment can take up
to 5 seconds.

NOTE: It is highly recommended to use a state-of-the-art

modem and leave it in its factory setting.