T7047C,G,H REMOTE SPACE SENSORS

3

62-0179

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a

hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage

Hazard.
Can shock individuals or short equipment

circuitry.
Disconnect power supply before installation.

Location

Locate the remote sensor about 5 ft (1.5m) above the

floor on an inside wall where it will be affected by freely
circulating air at average room temperatures.

Mounting

1. Loosen the cover locking screw with the Allen

wrench provided and remove the device cover.

2. Run wire to the selected location.

3. Thread wire through the semicircular hole in the

device.

4. Make connections to the T7047 (see the Wiring

section).

5. Select the proper screws for the application. Four

mounting screws are provided:

a. Two self-tapping type for wall mounting.
b. Two for outlet box mounting.

6. If air drafts occur through the wall opening,

eliminate with suitable material.

7. Fasten the T7047 on the wall or outlet box with

screws through the mounting holes in the device.

(See Fig. 2.)

8. Replace the cover and tighten the cover locking

screw.

Fig. 2. Mounting the T7047.

Fig. 3. T7047C1009 Remote Sensor resistance

change with change in temperature.

Fig. 4. T7047C1025 Remote Sensor resistance

change with change in temperature.

Fig. 5. T7047C1082 Remote Sensor resistance

change with change in temperature.

THERMOSTAT

MOUNTING
TAB SLOT (2)

WIRING
TERMINALS

MOUNTING
TAB (2 INSIDE
COVER)

COVER

MOUNTING
SCREW (2)

COVER LOCKING SCREW

OUTLET
BOX

M20072

2000

1800

1600

1400

1200

1000

10

20

30

40

50

60

70

80

90

100

RESISTANCE (OHMS)

1695 OHMS AT
75°F (24°C)

TEMPERATURE (DEGREES)

M3399

-10

0 10 20 30 40

°C

°F

2000

1800

1600

1400

1200

1000

10

20

30

40

50

60

70

80

90

100

RESISTANCE
(OHMS)

1420 OHMS AT
75 F (24 C)

TEMPERATURE (DEGREES)

M4034

-10

0 10 20 30 40

C

F

120K

100K

80K

60K

40K

20K

20

40

60

80

100

120

140

160

180

200

RESISTANCE (OHMS)

TEMPERATURE (DEGREES)

M3398

0 10 20 30 40

F

220

C

-7 50

60

70

80

90

100

22,800 OHMS AT
77 F (25 C)