Mounting:
3/8 in. (10 mm) to 1/2 in. (13 mm) square or round damper

shafts. Actuator can be mounted with shaft in any position.
Secure hub to shaft with:

ML8125, ML4125A,B: Four 1/4-28 UNF set screws. Use

1/8 in. Allen wrench to tighten set screws.

ML8135, ML4135: Two 1/4-28 UNF set screws. Use 1/8 in.

Allen wrench to tighten set screws.

ML4125C,D: Four 3 mm set screws. Use 3 mm Allen wrench

to tighten set screws.

IMPORTANT

Honeywell does not recommend using linkages with
these actuators because side-loading of the output
hub reduces actuator life.

Minimum Damper Shaft Length: 1-3/4 in. (45 mm).

Timing:
Drive Open:

ML4125, ML8125: 25 to 40 seconds (load dependant).
ML4135, ML8135: 20 to 25 seconds (load dependant).

Spring Close:

ML4125, ML8125: 20 to 25 seconds.
ML4135, ML8135: 15 seconds.

Design Life (at Rated Voltage):

ML4125, ML8125: 80,000 full-stroke cycles.
ML4135, ML8135: 60,000 full-stroke cycles.

Environmental Protection Ratings: See Table 2.

Table 2. Environmental Ratings.

Approvals: See Table 3.

Accessories:
201391 Shaft Adapter for 3/8 in. (10 mm) shafts.
205649 Mounting Bracket (included with the actuator).
32003532-001 Adjustable Switch Package, two 10A

externally-mounted fully-adjustable switches.

Table 3. Approvals.

Fig. 1. ML4125/4135, ML8125/8135

dimensiona drawing in in. (mm).

All Devices

ML4125C,D, ML8125, ML8135

NEMA1

IP54

ML4125

ML4135 ML8125 ML8135

A,B

C,D

UL/cUL

X

X

X

X

X

UL873
Plenum Rating,
File No. E4436

X

X

X

X

X

CE

X

X

X

C-TICK

X

X

2 (51)

1 (25)

5/8

(17)

6 3/8

(161)

7 1/2

(192)

4 (102)

7/8 (22)

5 1/8 (129)

2 (51)

3 5/16 (84)

1/16 (2)

M17538

ML4135/ML8135 HAVE SHORTER
HUB WITH TWO SET SCREWS.
ML4125/ML8125 HAVE LONGER
HUB WITH FOUR SET SCREWS.