Installation, Wiring, Caution – Honeywell ML4135 User Manual

Page 5: Warning

Advertising
background image

ML4125, ML4135, ML8125, ML8135 FAST-ACTING, TWO-POSITION ACTUATORS

5

63-2567—3

Installation

CAUTION

Device Malfunction Hazard.
Improper set screw tightening causes device
malfunction.
Tighten set screws with proper torque to prevent
damper shaft slippage.

CAUTION

Actuator Damage Hazard.
Using actuator as shaft bearing causes device
damage.
Use actuator only to supply rotational torque. Avoid
any side loads to actuator output coupling bearings.

To install actuator, proceed as follows:

1.

Place actuator over damper shaft; and hold mounting
bracket in place. See Fig. 2.

2.

Mark screw holes on damper housing.

3.

Remove actuator and mounting bracket.

4.

Drill or center-punch holes for mounting screws (or use
no.10 self-tapping sheet metal screws).

5.

Turn damper blades to desired normal (closed) position.

6.

Place actuator and mounting bracket back into position
and secure bracket to damper box with sheet metal
screws.

7.

Tighten set screws securely into damper shaft using
minimum 30 lb-in., maximum 60 lb-in. torque. Use
1/8 in. or 3 mm Allen wrench (see Specifications for
details) to tighten set screws.

Wiring

WARNING

Electrical Power Hazard.
Line voltage can cause death or serious injury
and short equipment circuitry.
Disconnect power supply before installation.

CAUTION

Electrical Shock or Equipment Damage Hazard.
Low voltage can shock individuals or short
equipment circuitry.
Disconnect power supply before installation.

IMPORTANT

1. All wiring must comply with local electrical codes,

ordinances and regulations.

2. Voltage and frequency of transformer used with

ML8125 or ML8135 must correspond with the
characteristics of power supply and actuator.

3. Use wires rated for at least 75°C (167°F).

See Fig. 4 through 6 for typical wiring diagrams.

Fig. 4. Typical 24 Vac wiring.

Fig. 5. Typical 120 Vac wiring.

Fig. 6. Typical 230 Vac wiring.

Table 4. Color Translations.

G

F

I

E

BROWN

BRAUN

BRUN

BRUNO

CAFE

BLUE

BLAU

BLEU

AZZURRO AZUL

BLACK

SCHWARZ NOIR

NERO

NEGRO

WHITE

WEISS

BLANC

BIANCO

BLANCO

RED

ROT

ROUGE

ROSSO

ROJO

L1

24 VAC

L2

RED

BLACK

R

W

M17585

( )

( )

L1

120

VAC

L2

WHITE

BLACK

R

W

M17589

( )

( )

L1

230

VAC

L2

BLUE

BROWN

R

W

M17588

( )

( )

Advertising
This manual is related to the following products: