J. Removal and Replacement of Headmaster (Condensing Pressure

Regulator - C.P.R.) - Remote Air-Cooled Model Only

IMPORTANT

Always install a new drier every time the sealed refrigeration system is opened.
Do not replace the drier until after all other repair or replacement has been
made.

1) Turn off the power supply.
2) Remove the panels from the remote condenser unit.
3) Recover the refrigerant and store it in an approved container.
4) Before heating, break off the stub on the dome to release the dome charge.
5) Disconnect the headmaster.
6) Place the new headmaster in position.
7) Remove the drier, then place the new drier in position.
8) Braze all fittings with nitrogen gas flowing at a pressure of 3 to 4 PSIG.

CAUTION

Always protect the headmaster body by using a damp cloth to prevent it from
overheating. Do not braze with the headmaster body exceeding 250°F (121°C).

9) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.

10) Evacuate the system and charge it with refrigerant. See the charge label in the machine

compartment for the required refrigerant charge.

11) Replace the panels in their correct positions.
12) Turn on the power supply.