T4398A,B PRECISION ELECTRIC HEATING THERMOSTAT

5

69-1604

OPERATION AND CHECKOUT

After the thermostat is installed and wired, check out normal
operation as follows:

1. Turn setting dial fully clockwise until the switch clicks

and the electric heater starts to heat.

2. Turn the dial fully counterclockwise; the power circuit

breaks and the electric heater starts to cool.

3. The T4398 is a more accurate thermostat, allowing

users to be more comfortable at lower setpoint settings

(saving energy and lowering heating costs). To deter-
mine final setting:

a. Begin with setting the dial indicator at 68°F (20°C).

b. After two operating hours, if not comfortable, adjust

setpoint to raise or lower the temperature, adjusting

temperature only a few degrees each time.

Calibration

IMPORTANT

Do not assume the thermostat is out of calibration

until it is installed and allowed to operate for several
hours.

The T4398 is accurately calibrated at the factory under
controlled conditions. The snap switch turns on heat when the

setpoint is raised to room temperature.

The vapor-filled diaphragm sensor is affected by barometric

pressure and altitude. Deviations up to 1°F (±1/2°C) are within

normal operation. The control point drops 2°F every 1000 ft
(1°C/300m) above sea level. See Fig. 5 and 6.

Fig. 5. T4398 altitude correction in (ft).

Fig. 6. T4398 altitude correction in (m).

To calibrate (see Fig. 7):

1. Remove cover and place it in a location that allows it to

sense the room temperature.

NOTE: Allow several minutes for the thermometer to stop

being affected by the heat from your hand.

2. Rotate the setpoint knob counterclockwise until you

hear the switch click.

3. Hold the setpoint knob firmly and rotate the setpoint

scale ring counterclockwise until 12 o’clock on the ring
is aligned with the thermometer cover.

4. The heat from your hand will affect the diaphragm sen-

sor so wait five minutes and verify the calibration.

10

8

6

0

1000

F

2000

ELEVATION IN FEET

SEA

LEVEL

3000

4000

5000

6000

4

2

0

LOS ANGELES

ATLANTA

LAS VEGAS

DENVER

M20353

101

99

95

93

89

0.4

KPa

ELEVATION

CITIES WITH

TEMPERATURE

CORRECTIONS

( C CORRECTIONS

TO BE ADDED)

INCREASING

B

A

R

OMETRIC PRESSURE

ELEVATION IN METERS

1.2 2.0 2.8 3.6 4.4 5.2 6.0

M20354

(SEA LEVEL)

WINNIPEG

CALGARY

0

240M

574M

677M

1079M

(FOR EXAMPLE, A
CORRECTION OF
APPROXIMATELY 3.5 C
WOULD BE INDICATED
FOR INSTALLATION
IN CALGARY.)

REGINA

EDMONTON