Broadcasting the service message, W7761a device status led – Honeywell W7761A User Manual

Page 37

Advertising
background image

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

37

74-2699

Table 9. Excel 10 Alarms.

Name of alarm or error bit

Alarm type

number

Meaning of alarm code or error bit

RETURN_TO_NORMAL

128U

Return to no alarm after being in an alarm condition. This code is added
numerically to another alarm code to indicate that the alarm condition has
returned to normal.

ALARM_NOTIFY_DISABLED

255U

The alarm reporting has been turned off by the DestManMode. No more

alarms are reported via nvoAlarm until DestManMode turns on alarm repor
or upon application restart.

NO_ALARM

0

No alarms presently detected.

INPUT_NV_FAILURE

1

One or more NV inputs have failed in receiving an update within their spec
FAILURE_DETECT_TIME.

NODE_DISABLED

2

The control algorithm has stopped because the RIO device is in

DISABLED_MODE, MANUAL, or FACTORY_TEST mode. No more alarms
reported when the device is in the DISABLED_MODE. Alarms continue to
reported if the device is in the MANUAL or FACTORY_TEST mode. The
control is shut down and disabled until power is cycled or the node is reset
See note 1 below.

SENSOR_FAILURE

3

One or more sensors have failed.

NOTE:

The node can be reset by switching the node to MANUAL and then to the normal operating mode.

Also, the Excel 10 variables,

AlarmLogX where X is 1 through 5, that store the last five alarms to occur in the device, are

available. These points can be viewed through XBS or E-Vision.

Broadcasting the Service Message

The Service Message allows a device on the E-Bus to be positively identified. The Service Message contains the device ID
number and, therefore, can be used to confirm the physical location of a particular Excel 10 in a building.
There are two methods of broadcasting the Service Message from an Excel 10 W7761A Device. One uses a hardware service
pin button on the side of the device (see Fig. 24). The other involves using the PC Configuration tool, as follows.

The commissioning tool is used to perform the ID Assignment task (see the E-Vision User’s Guide form, 74-2588).

M10094

SERVICE
PIN
BUTTON

Fig. 24. Location of the Service Pin Button.

W7761A Device Status LED

The LED on the front and center of a W7761A Device provides a visual indication of the status of the device. See Fig. 25.
When the W7761A receives power, the LED should appear in one of the following allowable states (see Table 10):

Advertising