Appendix b. sequences of operation, Common operations – Honeywell W7761A User Manual

Page 42

Advertising
background image

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

42

74-2699

displayed. Select the project and the Zone manager within that project that is being exported and the

Export button. Exit

CARE and Start E-Vision. Select the E-Vision project to open and the CARE Export Filename created previously. Once
the project is open, select the RIO device that the Digital Output is connected to and go into the Application Selection
screen (offline) by selecting the

Controller, Application Selection menu items. From the Outputs tab of the Application

Selection dialog box, select the first Unused_DigOutput and scroll up until Discrete1 is displayed and select it. Select the
OK button to save the selection.

4. Select the

Controller menu item and then Import from CARE to import the Zone Manager files with the new pseudo

analog point. If this function has already been performed before, the user will be prompted with the message

CARE

Export File has already been imported, do you want to import again?. Select Yes to continue with the Import. When the
import is finished, E-Vision displays the message

CARE Export File has been imported. Select OK to continue.

5. Select the

Network menu item and then Map C-Bus Points. Select RIO1 as the Controller Type from the Map C-Bus

Points dialog box. Under Unmapped CARE, select the name of the RIO device that the Digital Output was added to in
CARE. Under

Unmapped Excel 10, select the name of the RIO device that the actual Digital Output was added to (both

names should be the same). Next, select the

Custom button and the Custom Mapping CARE Points dialog box will be

displayed. Select the

MiscExhFan point under CARE Points and DigOut1Cmd under Excel 10. Select the Map button to

add the

MiscExhFan point to the list of Mapped Points. Click on the Close button to exit the Custom Mapping CARE

Points dialog box. Click on the Close button to exit the Map C-Bus Points dialog box.

6. Re-commission the RIO device that had the custom mapping done.
7. Select the Controller menu item and the Update Zone Manager Files. E-Vision will add the custom mapping information

to the Zone Manager files. When the Update Zone Manager Files function is done, close the E-Vision project and exit out
of E-Vision.

8. Start CARE and open the Zone Manager that was just updated through the Update Zone Manager Files function and

start XI584 by selecting the

Controller, Tools and XI584 menu items. Once XI584 is started, select the Utilities, File

Transfer menu items and select CARE Import. Select the project and the Zone Manager that was just updated and select
Import and click OK on the Select Target Controller dialog box. When the CARE Import is complete, close the CARE
Import dialog box. If this is the initial loading of the Zone Manager, then it will have to be reset and the CPU address set
by the XI581 Emulation function (

Applications, XI581 Emulation menu). Select the Utilities, File Transfer menu items and

select

Download. The Download dialog box will be displayed. Check the All selection and click the Controller button.

When the

Select Controller/Subsystem dialog box is displayed, make sure that the correct CPU address or name is

highlighted and select the

OK button. Click the Download button and Yes to the message Replace updated application

part in controller (CPU address or Controller name). When the download is complete, exit out of the

Download dialog

box. From the

XI584 main menu, select the Data, Access by User Address menu items. Type MiscExhFan in the Search

For User Address and click on the Search button. When the MiscExhFan point displays in the User Addresses list, click
on the point and select the

Attributes button. XI584 will now display the value of the Digital Output connected to the RIO

device. To command the

MiscExhFan to the On mode, put the point in the Manual mode and enter a value of 1.0 or

greater. To command the MiscExhFan to the Off mode, put the point in the Manual mode and enter a value of 0.0. This
point can now be used in the Zone Manager control strategy or switching logic and Time Programs. This point can be
used in other Excel 5000 controllers (C-Bus) by assigning a global analog point in the destination controller with the user
address name of MiscExhFan. Refer to the CARE User’s Manual form, 74-5587 for information on creating global points
in Excel 5000 controllers.

Table A-3. Supported Digital Output Types.

E-Vision Enumerated Name in the Output

Application Selection Tab

RIO Network Variable that contains the

Hardware Output Value

Float1_Open through Float8_Open (Series 60 -
requires two outputs assigned. Float1_Open
must be assigned before Float1_Close)

DigOut1Cmd through DigOut8Cmd

Float1_Close through Float8_Close (Series 60
- requires two outputs assigned. Float1_Open
must be assigned before Float1_Close)

DigOut1Cmd through DigOut8Cmd

Discrete1 through Discrete8 (Maintained On/Off
outputs)

DigOut1Cmd through DigOut8Cmd

Modulate1 through Modulate8 (PWM outputs)

DigOut1Cmd through DigOut8Cmd

Appendix B. Sequences of Operation.

Common Operations

The Excel 10 W7761A Device contains inputs and outputs, but no control software. All control that would be associated with
the inputs and outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable for
VAV control, temperature control, or any control function that would require less than a 30 second update rate. The analog and
digital sensors could be shared or bound to other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus
through the Excel 10 Zone Manager. This would allow the other Excel 10 controllers to use their physical inputs for monitoring
other elements such as return humidity, IAQ, etc. to achieve better control.

Room Temperature Sensor (RmTemp)