Honeywell W7761A User Manual

Page 45

Advertising
background image

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

45

74-2699

Table C1. Input/Output Points (Left).

Engineering Units:

English (Metric) or

Digital

State

or

Value

of

User Address

NvName

Field Name

States plus Range

State

Default

AI1RType

ncirioIoSelect

ResistiveIn0

DA_Temp_PT3000
OA_Temp_PT3000
RA_Temp_PT3000
Custom_PT3000
DA_Temp_20KNTC
RA_Temp_20KNTC
Space_Temp_T7770
Custom_20KNTC
Unused_Res_AI

0
1
2
3
4
5
6
7
255

Unused_Res_AI

AI2RType

ncirioIoSelect

ResistiveIn1

See AI1RType Eng. Units/States
column for selections

Unused_Res_AI

AI3RType

ncirioIoSelect

ResistiveIn2

See AI1RType Eng. Units/States
column for selections

Unused_Res_AI

AI4RType

ncirioIoSelect

ResistiveIn3

See AI1RType Eng. Units/States
column for selections

Unused_Res_AI

AI5VType

ncirioIoSelect

VoltageIn0

RA_Hum_C7600C
OA_Hum_C7600C
Filter_Diff_Pres
RA_Hum_C7600B
OA_Hum_C7600B
RA_Enthalpy
OA_Enthalpy
Space_CO2
Voltage_Monitor
Unused_Volt_AI

0
1
2
3
4
5
6
7
8
255

Unused_Volt_AI

AI6VType

ncirioIoSelect

VoltageIn1

See AI5VType Eng. Units/States
column for selections

Unused_Volt_AI

(continued)

Advertising