EXCEL 10 W7761A INPUT/OUTPUT DEVICE

54

74-2699

Table C1. Input/Output Points (Right Continued).

Share (SH), Map (MA), Direct Access (DA)

E-Vision (EV): Calibrate (C), Monitor (M),

Parameter (P), Schematic (S)

Hardware Configuration (HW),

Manual Point (MN), Test (TS)

SH

MA

DA

EV

HW

MN

TS

Comments

SrcDigIn2Sts: Refer to the description for SrcDigIn1Sts.

X

X

X

M

DI2State:
Refer to the description for DI1State.

SrcDigIn3Sts: Refer to the description for SrcDigIn1Sts above.

X

X

X

M

DI3State:
Refer to the description for DI1State.

SrcDigIn4Sts: Refer to the description for SrcDigIn1Sts above.

X

X

X

M

DI4State:
Refer to the description for DI1State.

X

X

X

M

SrcHumidAI5 is an output network variable corresponding to the voltage or current
input channel (AI5) if the selection for humidity sensor was made via ncirioIoSelect
for AI5.

X

X

X

M

SrcHumidAI6 is an output network variable corresponding to the voltage or current
input channel (AI6) if the selection for humidity sensor was made via ncirioIoSelect
for AI6.

X

X

X

M

SrcPressAI5 is an output network variable corresponding to the voltage or current
input channel (AI5) if the selection for a pressure sensor was made via
ncirioIoSelect for AI5.

X

X

X

M

SrcPressAI6 is an output network variable corresponding to the voltage or current
input channel (AI6) if the selection for a pressure sensor was made via
ncirioIoSelect for AI6.

X

X

X

M

SrcTempAI1 is an output network variable corresponding to the analog input
channel (AI1). This NV will contain AI1 temperature value with the OffsetCal1AI1
applied to it.

X

X

X

M

SrcTempAI2 is an output network variable corresponding to the analog input
channel (AI2). This NV will contain AI2 temperature value with the OffsetCal1AI2
applied to it.

X

X

X

M

SrcTempAI3 is an output network variable corresponding to the analog input
channel (AI3). This NV will contain AI3 temperature value with the OffsetCal1AI3
applied to it.

X

X

X

M

SrcTempAI4 is an output network variable corresponding to the analog input
channel (AI4). This NV will contain AI4 temperature value with the OffsetCal1AI4
applied to it.

X

X

X

M

SrcVoltageAI is an output network variable corresponding to the voltage or current
input channel (AI5 or AI6) if the selection for a voltage sensor was made via
ncirioIoSelect.