Honeywell W7761A User Manual

Page 57

Advertising
background image

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

57

74-2699

Table C3. Status Points (Left).

Engineering Units:

English (Metric) or

Digital

State

or

Value

of

User Address

NvName

Field Name

States plus Range

State

Default

AlarmNode

nvoAlarm

node

0 to 127

0

AlarmSubnet

nvoAlarm

subnet

1 to 255

0

AlarmType

nvoAlarm

type
0 to 255

NO_ALARM
INPUT_NV_FAILURE
NODE_DISABLED
SENSOR_FAILURE
rINPUT_NV_FAILURE
rNODE_DISABLED
rSENSOR_FAILURE
ALARM_NOTIFY_DISABLED

0
1
2
3
129
130
131
255

NO_ALARM

AlarmTypeLog0

nvoAlarmLog

type0

Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.

NO_ALARM

AlarmTypeLog1

nvoAlarmLog

type1

Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.

NO_ALARM

AlarmTypeLog2

nvoAlarmLog

type2

Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.

NO_ALARM

AlarmTypeLog3

nvoAlarmLog

type3

Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.

NO_ALARM

AlarmTypeLog4

nvoAlarmLog

type4

Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.

NO_ALARM

Errorbyte1

nvoError

error_bit(0)
Byte Offset = 0
Bit Offset = 0
ResSensor1Error(AI1)

FALSE
TRUE

0
1

FALSE

(continued)