EXCEL 10 W7761A INPUT/OUTPUT DEVICE

60

74-2699

Table C3. Status Points (Right Continued).

Share (SH), Map (MA), Direct Access (DA)

E-Vision (EV): Calibrate (C), Monitor (M),

Parameter (P), Schematic (S)

Hardware Configuration (HW),

Manual Point (MN), Test (TS)

SH

MA

DA

EV

HW

MN

TS

Comments

X

M

ResSensor2Error(AI2): Refer to the description of ResSensor1Error(AI1).

X

M

ResSensor3Error(AI3): Refer to the description of ResSensor1Error(AI1).

X

M

ResSensor4Error(AI4): Refer to the description of ResSensor1Error(AI1).

X

Software version.

A four byte ASCII string indicating the type of node (model).

X

Software version.

X

Software version.

The NodeType is a numeric identifier that is stored in EPROM that identifies the
Excel 10 node type. Whenever a new software version or upgrade is issued, this is
reflected in nroPgmVer which typically is read by a network management node to
identify the node type. The contents of nroPgmVer contain compatible model type
information and is fixed at the time when the node software is compiled.

CommFailure:
This field is not supported and is set to 0 (FALSE).

disabled: disabled reports 1 if nvoIO mode is set to DISABLED_MODE or
FACTORY_TEST mode. Otherwise disabled is set to 0.

ElectricalFault:
This field is not supported and is set to 0 (FALSE).

FailSelfTest:
This field is not supported and is set to 0 (FALSE).

FeedbackFailure:
This field is not supported and is set to 0 (FALSE).

InAlarm: If there are currently any active alarms reported by InAlarm, or InAlarm is
set to AlarmNotifyDisabled, then InAlarm is set to True, if not InAlarm is set to False.

InvalidId: If object_id is not a valid object, invalid_id is set to 1 (TRUE) otherwise it is
set to 0 (FALSE).

InvalidRequest: If object_request is not a valid request for the object addressed,
InvalidRequest is set to 1 (TRUE) otherwise it is set to 0 (FALSE).

(continued)