EXCEL 10 W7761A INPUT/OUTPUT DEVICE

65

74-2699

Table C4. Configuration Parameters (Left Continued).

Engineering Units:

English (Metric) or

Digital

State

or

Value

of

User Address

NvName

Field Name

States plus Range

State

Default

AIUpperLimit

nciEUConvrtRes

UpperLimitS7

degrees F -40 to 240
degrees C (-40 to 116)

0

DeltaC

nciDelta

deltacurrent

mA
0 to 256

0

DeltaCO2

nciDelta

deltaCO2

PPM 0 to 2000

0

DeltaH

nciDelta

deltahum

percent 0 to 163

0

DeltaP

nciDelta

deltapres

inw 0 to 32
kPa (0 to 7.97)

0

DeltaT1

nciDelta

deltatemp(0)

degrees F 0 to 256
degrees C (0 to 124)

0

DeltaT2

nciDelta

deltatemp(1)

degrees F 0 to 256
degrees C (0 to 124)

0

DeltaT3

nciDelta

deltatemp(2)

degrees F 0 to 256
degrees C (0 to 124)

0

DeltaT4

nciDelta

deltatemp(3)

degrees F 0 to 256
degrees C (0 to 124)

0

DeltaV

nciDelta

deltaVolt

0 to 10.5 volts

0

DO1FlSpeed

nciFloatConfig

DO0

seconds
0 to 900

90

DO2FlSpeed

nciFloatConfig

DO1

seconds
0 to 900

90

DO3FlSpeed

nciFloatConfig

DO2

seconds
0 to 900

90

DO4FlSpeed

nciFloatConfig

DO3

seconds
0 to 900

90

(continued)