EXCEL 10 W7761A INPUT/OUTPUT DEVICE

69

74-2699

Table C4. Configuration Parameters (Left Continued).

Engineering Units:

English (Metric) or

Digital

State

or

Value

of

User Address

NvName

Field Name

States plus Range

State

Default

DO6PWMPeriod

nciPWMConfig2

DO5.si_period_pwm

seconds 0.0 to 3000

25.6

DO6PWMZero

nciPWMConfig2

DO5.si_pnct_time

seconds 0.0 to 3000

0.1

DO6PWMFull

nciPWMConfig2

DO5.si_delta_time

seconds 0.0 to 3000

25.6

DO7PWMPeriod

nciPWMConfig2

DO6.si_period_pwm

seconds 0.0 to 3000

25.6

DO7PWMZero

nciPWMConfig2

DO6.si_pnct_time

seconds 0.0 to 3000

0.1

DO7PWMFull

nciPWMConfig2

DO6.si_delta_time

seconds 0.0 to 3000

25.5

DO8PWMPeriod

nciPWMConfig2

DO7.si_period_pwm

seconds 0.0 to 3000

25.6

DO8PWMZero

nciPWMConfig2

DO7.si_pnct_time

seconds 0.0 to 3000

0.1

DO8PWMFull

nciPWMConfig2

DO7.si_delta_time

seconds 0.0 to 3000

25.5

Table C4. Configuration Parameters (Right Continued).

Share (SH), Map (MA), Direct Access (DA)

E-Vision (EV): Calibrate (C), Monitor (M),

Parameter (P), Schematic (S)

Hardware Configuration (HW),

Manual Point (MN), Test (TS)

SH

MA

DA

EV

HW

MN

TS

Comments

X

M

X

DO6PWMPeriod: Refer to the description for DO1PWMPeriod.

X

M

X

DO6PWMZero: Refer to the description for DO1PWMPeriod.

X

M

X

DO6PWMFull: Refer to the description for DO1PWMPeriod.

X

M

X

DO7PWMPeriod: Refer to the description for DO1PWMPeriod.

X

M

X

DO7PWMZero: Refer to the description for DO1PWMPeriod.

X

M

X

DO7PWMFull: Refer to the description for DO1PWMPeriod.

X

M

X

DO8PWMPeriod: Refer to the description for DO1PWMPeriod.

X

M

X

DO8PWMZero: Refer to the description for DO1PWMPeriod.

X

M

X

DO8PWMFull: Refer to the description for DO1PWMPeriod.