EXCEL 10 W7761A INPUT/OUTPUT DEVICE

79

74-2699

Voltage to A/D

Sensor Voltage

0.00

0.00

0.50

0.25

1.00

0.50

1.50

0.75

2.00

1.00

2.50

1.25

3.00

1.50

3.50

1.75

4.00

2.00

4.50

2.25

5.00

2.50

5.50

2.75

6.00

3.00

6.50

3.25

7.00

3.50

7.50

3.75

8.00

4.00

8.50

4.25

9.00

4.50

9.50

4.75

10.00

5.00

0

0.50

1.00

1.50

2.00

2.50

3.00

3.50

4.00

4.50

5.00

100

0

300

500

700

900

200

400

600

800

1000

A/D VOLTS

VOLTS

SENSOR VOLTAGE VERSUS INPUT VOLTAGE TO A/D

M11612

Fig. E-10. Graph of Sensor Voltage versus input Voltage to A/D.

Sensor Type:
Third party.

Sensor Use:
Sensor Voltage (Vdc)/Pressure Inw (kPa) 2 to 10V, 0 to 5 inw (0 to 1.25 kPa).

Table E-11 lists the points for Sensor Voltage (Vdc) versus Pressure (Inw). Fig. E-11 shows the graph of these points.

Table E-11. Sensor Voltage (Vdc) Versus Pressure (Inw).

Pressure Inw (kPa)

Sensor Voltage (Vdc)

0.00 (0.00)

2.00

0.50.(0.13)

2.80

1.00 (0.25)

3.60

1.50 (0.37)

4.40

2.00 (0.5)

5.20

2.50 (0.62)

6.00