7-6

Item code

Item

No.

User

settings

Settings and descriptions

Factory default

settings

PA 24

Manipulated variable

deviation limit (CH2)

24

0.1 to 110.0% OUT/0.1 sec

110.0

PA 25

Time proportional output

cycle (CH2)

25

1 to 240 sec

10

PA 26

ON-OFF control Differential

(CH2)

26

0 to 1000 SPU (CH2)

50

PA 27

PID computation initialize

manipulated variable (CH2)

27

-5.0 to 105.0%

0.0

PA 28

Unused

28

[Description:]

Ò-----Óis displayed and setting cannot be performed.

-----

PA 29

Unused

29

-----

PA 30

Unused

30

-----

PA 31

Event on delay

Group 1 event number

31

0 to 16

[Description:]

A setting of 0 generates no delay.

0

PA 32

Event on delay

Group 1 delay time

32

0.0 to 3000.0sec

[Description:]

When

PA31

is set to 0, Т-----У is displayed and setting cannot be performed.

0.0

PA 33

Event on delay

Group 2 event number

33

0 to 16

[Description:]

A setting of 0 generates no delay.

0

PA 34

Event on delay

Group 2 delay time

34

0.0 to 3000.0sec

[Description:]

When

PA33

is set to 0, Т-----У is displayed and setting cannot be performed.

0.0

PA 35

Event on delay

Group 3 event number

35

0 to 16

[Description:]

A setting of 0 generates no delay.

0

PA 36

Event on delay

Group 3 delay time

36

0.0 to 3000.0sec

[Description:]

When

PA35

is set to 0, Т------У is displayed and setting cannot be performed.

0.0

PA 37

Event on delay

Group 4 event number

37

0 to 16

[Description:]

A setting of 0 generates no delay.

0

PA 38

Event on delay

Group 4 delay time

38

0.0 to 3000.0sec

[Description:]

When

PA37

is set to 0, Т-----У is displayed and setting cannot be performed.

0.0

PA 39

FAST X

39

0

PA 40

CP computation temperature

compensation

40

-1000 to +1000 PVU (CH1)

[Description:]

Т-----У is displayed for models without CP compensation

and setting can not be performed.

0

PA 41

Unused

41

[Description:]

Ò-----Óis displayed and setting cannot be performed.

0

PA 42

Unused

42

0

PA 43

PID computation initialize

(CH1)

43

0

PA 44

PV2 message display mode

44

0: CP or PO

2

value display

1: mV value display

2: O

2

sensor impedance value display

0

PA 45

G.SOAK time (CH1)

45

0.1 to 60.0sec

2.0

PA 46

G.SOAK time (CH2)

46

0.1 to 60.0sec

2.0

0 : 2X

1 : 10X

2 : 60X

3 : 120X

[Description:]

When setup data

C62

is set to 1 (program time unit: minutes,

seconds), settings 3 and 4 produce a speed of 10 X.

When

C62

is set to 2 (program time unit: 0.1sec), the FAST

mode is not available.

0: No initialization during advance processing and PID group

change.

1: Initializes during advance processing but not during PID

group change.

2: No initialization during advance processing but initializes

during PID group change

3: Initializes both during advance processing and PID group

change

Chapter 7. PARAMETER SETUP