7-9

Detailed information on variable parameters

PA01 (keylock)

0: keylock disabled
1: display of setup data setting disabled
2: display of all settings disabled
3: display of all settings disabled. Operation keys disabled

• The following keys are disabled when

PA01

is set to 1.

Normal display mode:

SETUP key

(setup data setting)

FUNC + CLR + MESSAGE keys

(general reset)

• The following keys are disabled when

PA01

is set to 2.

Normal display mode:

SETUP key

(setup data setting)

FUNC + CLR + MESSAGE keys

(general reset)

FUNC + PARA keys

(event configuration data setting)

PID key

(PID parameter setting/constant value
control data setting)

FUNC + PID keys

(constant value control data setting)

FUNC + PROG keys

(program setting)

+ PROG keys

(program copy)

LOAD key

(memory card load)

SAVE key

(memory card save)

• The following keys are disabled when

PA01

is set to 3 or to 2.

Normal display mode:

FUNC + DISP key

(display channel switching)

PROG key

(program selection)

RUN/HOLD key

(RUN operation/HOLD operation)

PROG + RUN/HOLD keys

(RESET operation)

PROG + DISP keys

(ADV operation)

FUNC +

keys

(FAST operation)

A/M key

(AUTO operation/MANUAL operation)

AT key

(AT start, AT cancel)

Note, however, that in the normal display mode in MANUAL mode MV can be
changed.

PA02 (memory protect)

0 : disabled
1 : program settings are protected
2 : setup, variable parameters and event configuration settings are

protected

3 : setup, variable parameters, event configuration settings and program

settings are protected

4 : setup, variable parameters, event configuration settings and PID

parameter settings are protected

5 : program settings and all parameter settings are protected

• When

PA02

is set to ≠ 0 (protect on), a general reset cannot be performed.