Honeywell DCP552 Mark II User Manual

Page 110

Advertising
background image

7-11

PA17 (PID computation initialize manipulated variable)

PA27 (PID computation initialize manipulated variable)

Under the conditions listed below, a PID computation starts using the value set in

PA17

.

• When there is a mode change from READY AUTO to RUN AUTO.
• When the controller is powered up in RUN (or HOLD, FAST, END) AUTO

mode.

• When auto-tuning ends.
Since the PV, SP and PID parameters affect a PID computation, the first
manipulated variable of a PID computation may not be the same as the value set in

PA17

and

PA27

.

PA31 to PA38 (event on delay groups 1 to 4, event/delay time)

• On delay can be performed on up to 4 events.

PA31

,

PA33

,

PA35

and

PA37

determine which events are to be processed.

• In a code event involving several event outputs, event on delay has to be set

separately for each output.

• All processes including event output standby on/off are processed before on

delay processing. When the event output ON condition remains on for longer
than the on delay time, the event output stays on.

• This is shown in the diagram below.

PA43 (PID computation initialize)

PA96 (PID computation initialize)

When SP changes abruptly due to ADV, the derivative action of a PID
computation, may cause an excessive change in the manipulated variable of the
computation.
For this reason, the initialization of a PID computation is performed to suppress an
excessive change.
But the initialization of a PID computation means that PID computation continuity
is lost which may affect operating conditions.

PA43

and

PA96

settings allow the

user to turn on or off initialization and determine its conditions.

Time

Event output turns on

Event output turns off

Event output turns off

On delay time

The requirement event turns on

The requirement event turns off

The requirement

event turns off

Chapter 7. PARAMETER SETUP

Advertising