Honeywell DCP552 Mark II User Manual

Page 124

Advertising
background image

7-25

0 to 16

: t/c

48 to 52 : linear (DC current, DC voltage)

64 to 71 : RTD

96 to 103: RTD

128 to 134: linear (DC current, DC voltage)

135

: O

2

Sensor

[Description:]

Setting 135 cannot be made on a model without CP

compensation. A model with CP compensation is tied to

setting 135. For details see range numbers listed in

Section 2-3, ÒInput Types and Range NumbersÓ (page 2-8).

0

C 11

11

PV2 range number

0: ûC Celsius

1: ûF Fahrenheit

[Description:]

When the

C01

setting is set to linear or O

2

sensor, [----]

is displayed and setting cannot be performed.

0

C 12

12

PV2 temperature unit

0 to 2

A setting of 0 means no decimal point and a setting of 1 and 2

indicates the number of decimal digits.

[Description:]

When the

C11

setting is set to linear or O

2

sensor, [----] is

displayed and setting cannot be performed.

The setting range varies with the

C11

and

C12

setting.

¥ A setting between 0 and 2 can be made when

C11

is set to:

and

C12

is set to 0.

C11

settings: 66, 68, 69, 98, 100, 101 and

C12

is set to 1.

¥ A setting of 0 and 1 can be made when

C11

is set to: 0 to 4,

6, to 14, 16, 64, 70, 71, 96, 102, 103and

C12

is set to 0,

when

C11

is set to: 0 to 5, 7, 8, 10, 12 to 14, 16, 64, 65, 67,

70, 71, 96, 97, 99, 102, 103and

C12

is set to 1.

¥ Only a setting of 0 is possible when

C11

is set to: 6, 9, 11

and

C12

is set to 1 .

¥ When the

C11

setting is for t/c or RTD, this setting is

reflected in PVU (PV2) units.

1

C 13

13

PV2 decimal point position

0 to 4

A setting of 0 means no decimal point and a setting

between 1 and 4 indicates the number of decimal digits.

[Description:]

When the

C11

setting is set to t/c, RTD, or O

2

sensor, [---

-] is displayed and setting cannot be performed.

When setting

C11

is linear, this setting is reflected in

PVU (PV2) units.

1

C 14

14

PV2 linear decimal point

position

0 PVU

C 15

15

PV2 linear range lower limit

10000PVU

C 16

16

PV2 linear range upper limit

0: Yes (compensated internally)

1: No (compensated exernally)

[Description:]

When the

C11

setting is set to RTD, linear or O

2

sensor, [----] is

displayed and setting cannot be performed.

0

C 17

17

PV2 cold junction

compensation

0: No

1: Yes

[Description:]

When the

C11

setting is set to t/c, RTD or O

2

sensor, [----] is

displayed and setting cannot be performed.

0

C 18

18

PV2 square root extraction

0.2 to 10.0 % (ratio depends on input range)

[Description:]

When the

C11

setting is set to t/c, RTD or O

2

sensor, [----] is

displayed and setting cannot be performed.

0.2

C 19

19

PV2 square root extraction

dropout

-1.0 to +1.0ûC

[Description:]

When the

C11

setting is set to RTD, linear or O

2

sensor, [----] is

displayed and setting cannot be performed.

Use 0.0 for normal settings.

0.0

C 20

20

PV2 cold junction bias

Item code

Item

No.

User

settings

Settings and descriptions

Factory default

settings

Ð19999 to +20000 PVU (PV2)

[Description:]

When the

C11

setting is set to t/c, RTD, or O

2

sensor, [---

-] is displayed and setting cannot be performed.

Reversing the lower limit and upper limit makes it

possible to reverse analog inputs and specified values.

Chapter 7. PARAMETER SETUP