Honeywell DCP552 Mark II User Manual

Page 128

Advertising
background image

7-29

0 to 127

[Description:]

Т----У is displayed for model without communications and

when

C97

is set to a value that is not equal to 0 and

setting cannot be performed.

When

C76

is set to 0, the communication function is not

activated.

0

C 76

76

Communication address

0: 9600bps

1: 4800bps

2: 2400bps

3: 1200bps

[Description:]

Т----У is displayed for model without communications and

when

C97

is set to a value that is not equal to 0 and

setting cannot be performed.

0

C 77

77

Transmission rate

0: 8 bits, even parity, 1 stop bit

1: 8 bits, no parity, 2 stop bits

[Description:]

Т----У is displayed for model without communications and

when

C97

is set to a value that is not equal to 0 and

setting cannot be performed.

0

C 78

78

Transmission code

0: CPL

1: ST221 (no PV trend)

2: ST221 (PV trend)

[Description:]

Т----У is displayed for model without communications and

when

C97

is set to a value that is not equal to 0 and

setting cannot be performed.

0

C 79

79

Communication

0 : RS-485

1 : RS-232C

[Description:]

Т----У is displayed for model without communications and

when

C97

is set to a value that is not equal to 0 and

setting cannot be performed.

0

C 80

80

Communication method

[Description:]

Can only be referenced for mechanical service use.

Ð

C 81

81

ROM ID

Ð

C 82

82

ROM ITEM

Ð

C 83

83

ROM revision

Ð

C 85

85

CPU board ID

Ð

C 86

86

I/O board ID

[Description:]

Т-----У is displayed and setting cannot be performed.

----

C 87

87

Unused

----

C 88

88

Unused

----

C 89

89

Unused

1

C 90

90

PID type

0: Yes

1: No

0

C 91

91

PV1 burnout

0: Yes

1: No

0

C 92

92

PV2 burn out

0: Does not go on a second time off in time proportional cycle.

1: Goes on a second time in time proportional cycle.

0

C 93

93

Time proportional output

0: Does not go on a second time off in time proportional cycle

1: Goes on a second time in time proportional cycle

0

C 94

94

Time proportional output

Ð

C 84

84

Data version

Item code

Item

No.

User

settings

Settings and descriptions

Factory default

settings

2 to 22mA
2 to 22mA

15

C 95

95

Voltage output control (CH1)

15

C 96

96

Voltage output control (CH2)

0 to 15

The backplate terminal is used when set to 0.

The loader jack is used for settings 1 to 15.

[Description:]

When set to 0, communications cannot be performed on

model without communications.

When set to 0, communications conditions are selected

using

C76

to

C80

.

The communication address is used for settings 1 to 15.

4800bps, 8 bits, even parity, 1 stop bit

0

C 97

97

Communications port

0 to 255

[Description:]

A setting of 0 is normally used.

0

C 98

98

Special function

0: Improved

1: Compatible with MarkI

Chapter 7. PARAMETER SETUP

Advertising