Detailed descriptions of setup data settings – Honeywell DCP552 Mark II User Manual

Page 130

Advertising
background image

7-31

Detailed descriptions of setup data settings

C07 (PV1 cold junction compensation)

C17 (PV2 cold junction compensation)

• This is a selection for cold junction compensation for thermocouples.

• When set to 1, perform 0°C compensation using a cold junction compensation

device outside the

DCP552.

C08 (PV1 square root extraction)

C09 (PV1 square root extraction dropout)

C18 (PV2 square root extraction)

C19 (PV2 square root extraction dropout)

• Flow pressure detected by the orifice of a normal differential pressure type

flowmeter is proportional to the power 2 of the flow rate signal. Consequently,
square root extraction is used when a uniform signal is needed.
When the input in the square root extraction is

C09

or less than the dropout set

in

C19

, an output of 0% can be obtained in the square root process.

• Square root extraction is not performed when

C08

and

C18

are set to 0.

C46 (auxiliary output 1 lower limit)

C47 (auxiliary output 1 upper limit)

C49 (auxiliary output 2 lower limit)

C50 (auxiliary output 2 upper limit)

• This is the scaling setting of the auxiliary output. The high and low values for

the upper and lower limits can be reversed.

• The example below shows that the output from auxiliary output 1 is 12mA

when MV is 100% and 20mA when MV is 0%. As shown, a 200% MV value is
required to generate an output of 4mA.
Thus

C46

is set to 200.0 and

C47

is set to 0.0.

200%

Auxiliary output 1

MV

20mA

100%

12mA

4mA

100%

100%

Output of root extraction (Y)

Dropout value

(0.2 to 10.0% variable)

Input (X)

Y= (X/100)

1/2

×

100

Chapter 7. PARAMETER SETUP