Setting event items

Handling Precautions

Events assigned to the selected channel can be displayed.

Note that when setup data C57 is set to 1, event items on the programming

map are skipped and not displayed.

When the event is a PV event

(1) In the set value display state, move to the segement event item to be set on the

programming map.

(2) Press the

ENTER key

to make display panel 1 flash (registration of first

setting).

(3) Use the

↑, ↓, ←, and →

keys

to make the first setting – setting the event

operating point.

Setting range : OFF –19999 to +20000 SPU

: OFF 0 to 20000 SPU (for absolute value deviation events)

: OFF –5.0 to +105.0% (for MV events)

(4) Press the

ENTER key

to stop the flashing on display panel 1. (Pressing the

FUNC

and

CLR keys

causes display panel 1 to return to unset state “-----”

and the flashing stops.)

Display (PV events)

Unset values are indicated as “ ----- ”.

NOTE

A PV event setting consists of a setting (including OFF) and a subfunction. A

subfunction cannot be used when a setting has not been made “ ----- ”.

PROG

SEG

PROFILE

Program

number

Segment

number

Set operating point

Pattern trend

Event number

Event type

Chapter 8. PROGRAM SETUP