8-9

When the event is a code event

(1) In the set value display state, move to the event item to be set for the segment

on the programming map.

(2) Press the

ENTER key

to make display panel 1 flash (registration of first

setting).

(3) Use the

↑, ↓, ←, and →

keys

to make the first setting – setting the event

output code.

Setting range : 0 to 2

n

– 1

(n indicates the number of output points set in event

configuration 1 auxiliary setting 1.)

(4) Press the

ENTER key

to stop the flashing on display panel 1.

(Pressing the

FUNC

and

CLR keys

causes display panel 1 to return to unset

state “-----” and the flashing stops.)

Display (code event)

Unset values are indicated as “-----”.

NOTE

Code events use one subfunction. A subfunction cannot be used when a setting has

not been made “-----”.

Events that follow the event number of a code event (number of output points less

1) are skipped and not displayed.

PROG

SEG

PROFILE

Program

number

Segment

number

Output code setting

Pattern trend

Event number

Event type and No. of outputs

Chapter 8. PROGRAM SETUP