Honeywell DCP552 Mark II User Manual

Page 145

Advertising
background image

8-10

When the event is a timer code event

(1) In the set value display state, move to the event item to be set for the segment

on the programming map.

(2) Press the

ENTER key

to make display panel 1 flash (registration of first

setting).

(3) Use the

↑, ↓, ←, and →

keys

to make the first setting (output code).

Setting range: 0 to 2

n

– 1

(n indicates the number of output points set in event

configuration 1 auxiliary setting 1.)

(4) Press the

ENTER key

to stop the flashing on display panel 1 and display

panel 2 starts flashing. (Start of second setting)

(Pressing the

FUNC

and

CLR keys

causes display panel 1 and 2 to return to

unset state “-----” and the flashing stops.)

(5) Use the

↑, ↓, ←, and →

keys

to make the second setting (time).

Setting range:

0:00 to 500:00, 0.0 to 3000.0

(Time units are selected using setup data

C64

to set Hour/min, Min/sec, 0.1

sec. Since a colon “

:

” cannot be displayed, the decimal point is used instead.)

(6) Press the

ENTER key

to stop the flashing on display panel 2.

(Pressing the

FUNC

and

CLR keys

causes display panel 1 and 2 to return to

unset state “-----” and the flashing stops.)

Display (Code event with a timer function)

Unset values are indicated as “-----”.

NOTE

Timer code events use one subfunction. A subfunction cannot be used when a

setting has not been made “-----”.

Events that follow the event number of a timer code event (number of output

points less 1) are skipped and not displayed.

PROG

SEG

PROFILE

Program

number

Segment

number

Event number and sub number

Event type and No. of outputs

Set time value

Output code setting

Pattern trend

Chapter 8. PROGRAM SETUP

Advertising