Setting g.soak (guarantee soak) items – Honeywell DCP552 Mark II User Manual

Page 148

Advertising
background image

8-13

Setting G.SOAK (Guarantee soak) items

(1) In the set value display state, move to the G.SOAK item to be set for the

segment on the programming map.

(2) Press the

ENTER key

to make display panel 1 flash (registration of first

setting).

(3) Use the

↑, ↓, ←, and →

keys

to make the first setting – setting the G.SOAK

type.

Setting range: 0 to 3

0: No G.SOAK

1: First G.SOAK segment

2: Last G.SOAK segment

3: Entire G.SOAK segment

(4) Press the

ENTER key

to stop the flashing on display panel 1 and display

panel 2 starts flashing. (Start of second setting)

Note, however, that when the first setting is 0, “-----” is shown in the second

panel which does not flash.

(Pressing the

FUNC

and

CLR keys

causes display panel 1 and 2 to return to

unset state “

g.S.0/

-----” and the flashing stops.)

(5) Use the

↑, ↓, ←, and →

keys

to make the second setting (G.SOAK width).

Setting range: 0 to 1000 SPU

(6) Press the

ENTER key

to stop the flashing on display panel 2.

(Pressing the

FUNC

and

CLR keys

causes display panel 1 and 2 to return to

unset state “

g.S.0/

-----” and the flashing stops.)

Display

Unset values are indicated as “

g.S.0/

-----”.

When setup data

C59

is set to 1, a G.SOAK item on the programming map is

skipped and not displayed.

NOTE

When a G.SOAK setting is something other than 0, it uses a subfunction.

A subfunction cannot be used when a setting has not been made “

g.S.0/

-----”.

PROG

SEG

PROFILE

Program

number

Segment

number

Set G.SOAK type value

Pattern trend

G. SOAK TYPE

BAND

Set G.SOAK width value

Chapter 8. PROGRAM SETUP