8-15

Setting repeat items

(1) In the set value display state, move to the repeat item to be set for the segment

on the programming map.

(2) Press the

ENTER key

to make display panel 1 flash (registration of first

setting).

(3) Use the

↑, ↓, ←, and →

keys

to make the first setting – setting the number of

the return segment.

Setting range: 0 to segment number in setting

(4) Press the

ENTER key

to stop the flashing on display panel 1 and display

panel 2 starts flashing. (Start of second setting)

Note, however, that when the first setting is 0, “-----” is shown in the second

panel which does not flash.

(Pressing the

FUNC

and

CLR keys

causes display panel 1 and 2 to return to

unset state “

rP.0/

-----” and the flashing stops.)

(5) Use the

↑, ↓, ←, and →

keys

to make the second setting (repeat segment

times).

Setting range: 1 to 10000

(6) Press the

ENTER key

to stop the flashing on display panel 2.

(Pressing the

FUNC

and

CLR keys

causes display panel 1 and 2 to return to

unset state “

rP.0/

-----” and the flashing stops.)

Display

Unset values are indicated as “

rP.0/

-----”.

When setup data

C59

is set to 1, a repeat item on the programming map is

skipped and not displayed.

NOTE

When the number of return segment is something other than 0, it uses a

subfunction.

A subfunction cannot be used when a setting has not been made “

rP.0/

-----”.

PROG

SEG

PROFILE

Program

number

Segment

number

Pattern trend

R E P E A T S E G M E N T

T I M E S

Set repeat count value

Set number of return segment

Chapter 8. PROGRAM SETUP

Advertising