9-9

Chapter 9. MEMORY CARD OPERATIONS

Procedures for loading event configuration data

This procedure loads event configuration data on the memory card onto the

DCP552

.

Procedures for loading all parameters

This procedure loads all parameters on the memory card onto the

DCP552

.

Handling Precautions

The DCP552 Mark

II

and the old model, DCP552, differ in how some setup

data items are processed and the range of variable parameter PA15. Thus

the following changes have to be made when setup data, variable

parameters or all parameters saved on a DCP552 are loaded onto a

DCP552 Mark

II

.

• Setup data

: C21, C22, C45 to C50, C80, C90 to C97

• Variable parameters : PA15, PA25

Setup data and all parameters stored on a DCP552 Mark

II

cannot be

loaded onto a DCP552. (A loading attempt generates card error 16.)

Data delete check

D e l e t e O l d D a t a

L O A D ?

Load completed

LOAD key

A l l P a r a m e t e r s

L O A D G o o d

DISP key

Normal display mode

(Load operation is not performed.)

DISP key

Normal display mode

Data delete check

D e l e t e O l d D a t a

L O A D ?

Load completed

LOAD key

E V E N T D a t a

L O A D G o o d

DISP key

Normal display mode

(Load operation is not performed.)

DISP key

Normal display mode