11-3

Item

Specifications

Mode

Control section

Output section

Program run mode

READY

RUN

HOLD

FAST

END

READY FAST

Proportional band (P)

PID control

0.0 to 1000.0% (0.0: On-off control)

Integral time (I)

0 to 3600s (0: PD control)

Derivative time (D)

0 to 1200s (0: PI control)

Manipulated variable

limit

Low-limit : Ð5.0 to high-limit%

High-limit : Low-limit to +105.0%

Manual reset

0.0 to 100.0%

Auxiliary output

Auto tuning

Automatic setting of PID value by limit cycle method

Manipulated variable change 0.1 to 110.0%/0.1s

On-off control differential 0 to 1000U

Scaling

Possible

Type

SP1, PV1, deviation 1, MV1, SP2, PV2, deviation 2,

O

2

sensor mV value

PID groups selection

Segment specified, automatic zone selectable during

program run

No. of PID groups

16 groups for program operation (9 segment specific

and 7 automatic zone selecting)

Fixed command control

mode

READY

: Preparation state (control stop)

RUN

: Run state

AUTO

: Automatic run state

MANUAL: Manual run state (output is operatable to console)

AUTO

: Automatic run state

MANUAL: Manual run state (Enables manual output from system console.)

Normal reverse operation selection Selection is settable

Current output (5G)

CH1,CH2

Auxiliary output CH1, CH2

Output current

Allowable load resistor

Output accuracy

Output resolution

Max. output current

Min. output current

Output update cycle

Open time terminal voltage

: Preparation state (control stop, select of program number is possible.)

: Advancing run state

: Hold run state

: Fast feed run state

: End point run state

: Preparation and the fast feed state

: 4 to 20mA DC

: Lower than 600½ (under operating conditions)

: Lower than ± 0.1% FS (under standard conditions)

: 1/10000

: 21.6mA DC

: 2.4mA DC

: 0.1s

: Lower than 25V

Voltage output (6D)

CH1,CH2

Allowable load resistor

Load current adjustment

Open time terminal voltage

Off time leakage current

Output response time

Output resolution

Time proportional cycle

: Lower than 600½ (under the action conditions)

: 2 to 22mA variable

: Lower than 25V

: Lower than 100

µ

A

: Lower than 0.5ms on on-off 600½ load

Lower than 0.5ms off-on 600½ load

: 1/1000

: 1 to 240s variable

Chapter 11. SPECIFICATIONS