Item

Specifications

Output section

Event output

section

Open collector output

PV-based

Event type

PV, deviation, deviation with standby, absolute value

deviation, absolute value deviation with standby, PV

deviation rate, SP, MV, G.SOAK absolute value

deviation, G.SOAK absolute value deviation with

standby, normal PV1 operation, normal PV2 operation

Time-based

Time event, RAMP-E time monitoring, segment time,

program time

Code-based

Code event, timer-bearing code event, program number

binary code, segment number binary code, program

number BCD code, segment number BCD code

Mode-based

Specified segment, RUN + HOLD + END + FAST,

HOLD, READY + READY FAST, END, G.SOAK wait,

MANUAL, AT execution, FAST + READY + FAST,

console operation, RUN, advance, all alarm, PV range

alarm, O

2

sensor error, voltage drop

Network

Multidrop

(,+2## provided with only slave node functionality.)

1 to 31 units max.

Data flow

Half-duplex

Sync.system

Start-stop sync.

Transmission system

Balanced type (differential)

Data line

Bit serial

Signal line

Transmit and receive 5 lines (3 wires are connectable)

Communication speed 1200, 2400, 4800, 9600 bps selectable
Communication distance Max.500m (total sum)

300m in case of MA500 DIM connection

Others

Conforms to RS-485 standard

Character composition 11 bits/character
Format

1 start bit, even parity, 1 stop bit or

1 start bit, no parity, 2 stop bit

Set 0 to 1000U with PV-based

Event hysteresis

0.0 to 3000.0 are settable for 4 point event

Event on delay

Open collector output (8D)

CH1,CH2

External supply voltage

Max.load current

Off time leakage current

On time residual voltage

Output resolution

Time proportional cycle
External supply voltage

Max.load current

Max.common current

Off time leakage current

On time residual voltage

Communi-

cation

RS-485

: 12 to 24V DC

: 100mA/point

: Lower than 0.1mA

: Lower than 2V

: 1/1000

: 1 to 240s variable
: 12 to 24V DC

: 70mA/point

: 500mA

: Lower than 0.1mA

: Lower than 2V

RS-485 communications can be performed by connecting to a computer equipped with an RS-485 interface.

Data length

8 bits

Isolation

All inputs and outputs except external switch inputs are

completely isolated.

Chapter 11. SPECIFICATIONS