Page 204

Advertising
background image

12-14

Cold junction sensor calibration

Scroll

,

,

,

, keys

to show (

2022

) on upper display, then press

ENTER

key

.

The cold junction input 0% (CH1)

(1)

Press

SETUP key

until the PROG/SEG display shows (

02-01

).

(2)

Connect the millivolt source between (55)(–) and (56)(+), and then input 0.2V

(See Figure 12-10).

(3)

Press

ENTER key

after display stabilizes, AD count is shown on lower

display.

The cold junction input 100% (CH1)

(1)

Press

SETUP key

until the PROG/SEG display shows (

02-02

).

(2)

Connect the millivolt source between (55)(–) and (56)(+), and then input 1.0V

(See Figure 12-10).

(3)

Press

ENTER key

after display stabilizes, AD count is shown on lower

display.

The cold junction AD count data (CH1)

(1)

Press

SETUP key

until the PROG/SEG display shows (

02-03

).

(2)

Press

ENTER key

after display stabilizes, AD count is shown on lower

display.

The cold junction temperature data (CH1)

(1)

Press

SETUP key

until the PROG/SEG display shows (

02-04

).

(2)

Connect the thermometer (55).

(3)

Scroll

,

,

,

, keys

to set above temperature value.

(4)

Press

ENTER key

.

The cold junction input 0% (CH2)

(1)

Press

SETUP key

until the PROG/SEG display shows (

02-05

).

(2)

Connect the millivolt source between (58)(–) and (59)(+), and then input 0.2V

(See Figure 12-10).

(3)

Press

ENTER key

after display stabilizes, AD count is shown on lower

display.

The cold junction input 100% (CH2)

(1)

Press

SETUP key

until the PROG/SEG display shows (

02-06

).

(2)

Connect the millivolt source between (58)(–) and (59)(+), and then input 1.0V

(See Figure 12-10).

(3)

Press

ENTER key

after display stabilizes, AD count is shown on lower

display.

The cold junction AD count data (CH2)

(1)

Press

SETUP key

until the PROG/SEG display shows (

02-07

).

(2)

Press

ENTER key

after display stabilizes, AD count is shown on lower

display.

The cold junction temperature data (CH2)

(1)

Press

SETUP key

until the PROG/SEG display shows (

02-08

).

(2)

Connect the thermometer (58).

(3)

Scroll

,

,

,

, keys

to set above temperature value.

(4)

Press

ENTER key

.

Chapter 12. CALIBRATION