Dcp552 parameter work sheet – Honeywell DCP552 Mark II User Manual

Page 210

Advertising
background image

User name

:

Preparation date

:

Equipment name

:

Product name

:

Model No.

:

DCP552

Tag name

:

Instrumentation staffer in charge :

Business staffer in charge :

1

DCP552 Parameter Work Sheet

Variable parameter setting

No. Item code

Item

Factory default User

Settings and descriptions

settings

settings

1

PA 01

Key lock

0

0 : Keylock disabled
1 : Display of setup data settings disabled
2 : Display of all settings disabled
3 : Display of all settings disabled. Operation keys disabled.

2

PA 02

Memory protect

0

0 : Disabled
1 : Program settings are protected.
2 : Setup, variable parameters and event configuration

settings are protected.

3 : Setup, variable parameters, event configurations

and program settings are protected.

4 : Setup, variable parameters, event configurations

and PID parameter settings are protected.

5 : Program settings and all parameter settings are protected.

3

PA 03

Display channel setting

0

0 : 2 items are displayed for the selected CH
1 : Simultaneous 2CH display of the same item

4

PA 04

Synchronous 2 channel

0

0 : asynchronous

operation

1 : synchronous

5

PA 05

Program auto load

0

0 : OFF
1 : ON

8

PA 08

Auto-tuning (CH1)

0

0 : AT not performed
1 : Standard AT performed on currently used PID group

in mode other than READY mode

2 : AT writing overshoot-proof PID values to currently used

PID groups in mode other than READY mode performed

3 : Standard AT performed on PID groups A1 to A7 in

READY mode

4 : AT writing overshoot-proof PID values to PID groups

A1 to A7 in READY mode continuously performed

9

PA 09

Auto-tuning MV lower limit (CH1)

0.0

–5.0 to upper limit %

10

PA 10

Auto-tuning MV higher limit (CH1) 100.0

Lower limit to +105%

11

PA 11

SP bias (CH1)

0 SPU

–10000 to +10000 SPU (CH1)

12

PA 12

PV digital filter (CH1)

0.0

0.0 to 120.0sec

13

PA 13

PV bias (CH1)

0 PVU

–1000 to +1000 PVU(PV1)

14

PA 14

Manipulated variable deviation 110.0

0.1 to 110.0% OUT / 0.1sec

limit (CH1)

15

PA 15

Time proportional output cycle (CH1) 10

1 to 240sec

16

PA 16

On-off control differential (CH1) 50 SPU

0 to 1000 SPUm (CH1)

17

PA 17

PID computation initialize

0.0

–5.0 to +105.0%

manipulated variable (CH1)

21

PA 21

SP bias (CH2)

0

-10000 to +10000 SPU (CH2)

22

PA 22

PV digital filter (CH2)

0.0

0.0 to 120.0sec

23

PA 23

PV bias (CH2)

0 PVU

–1000 to +1000 PVU(PV2)

24

PA 24

Manipulated variable

110.0

0.1 to 110.0% OUT/0.1 sec

deviation limit (CH2)

25

PA 25

Time proportional output

10

1 to 240sec

cycle (CH2)

26

PA 26

ON-OFF control differential

50

0 to 1000 SPU (CH2)

(CH2)

27

PA 27

PID computation initialize

0.0

-5.0 to +105.0%

manipulated variable (CH2)

31

PA 31

Group 1 event number

0

0 to 16
(0: No delay is specified.)

32

PA 32

Group 1 delay time

0.0

0.0 to 3000.0sec

33

PA 33

Group 2 event number

0

0 to 16
(0: No delay is specified.)

34

PA 34

Group 2 delay time

0.0

0.0 to 3000.0sec

35

PA 35

Group 3 event number

0

0 to 16
(0: No delay is specified.)