Handling precautions – Honeywell DCP552 Mark II User Manual

Page 24

Advertising
background image

2-9

DC current, DC voltage

* •The O

2

sensor is manufactured by one of the following companies: Nihon Gaishi (NGK), Marathon

Monitors, Cambridge, Corning, AACC (Advanced Atmosphere Control Corporation), Barber

Colman or Furnace Control.

•PV2 in models with carbon potential compensation is tied to the O

2

sensor.

Handling Precautions

•The unit for code Z06 is “K” (kelvin).

•Code F50 and P50 do not generate the PV lower limit alarm.

•The number of decimal digits for DC current and DC voltage is

programmable from 0 to 4.

•The O

2

sensor generates the PV upper limit alarm at values of 1375mV or

above, but does not generate the PV lower limit alarm.

Chapter 2. NAMES AND FUNCTIONS OF PARTS

mV

Input type

Symbol

Code

Accuracy (under standard conditions)

±

0.1%FS

Input range (FS)

Range No.

mA

C01

4 to 20mA

48

Programmable range

-19999 to +20000

(Decimal point

position is variable.)

±

0.1%FS

(Linear)

(Linear)

Z51

2.4 to 20mA

52

±

0.1%FS

M01

0 to 10mV

49

±

0.1%FS

L02

-10 to +10mV

50

±

0.1%FS

0 to 100mV

51

±

0.1%FS

mA

C01

4 to 20mA

128

±

0.1%FS

(Linear)

Z51

2.4 to 20mA

134

±

0.1%FS

V

O

2

sensor *

0 to 1V

129

±

0.1%FS

(Linear)

-1 to +1V

130

±

0.1%FS

V01

1 to 5V

131

±

0.1%FS

0 to 5V

132

±

0.1%FS

–0.1%FS

0 to 10V

0 to 1250mV

Carbon potential (CP value)
indication range:
0.000 to 4.000% C
(Note, however, that PID control
is calculated over the 0.000 to
2.000% input range)
Oxygen pressure indication range:
0.000 to 1.500 x 10

-20

atm

133

135

When converted to mV values