4 - 5

Power Supply and Grounding

4-6

Power supply

To supply power to the

DCP552

, use an instrument-dedicated single-phase power

supply subject to minimal electrical interference.

Handling Precautions

If electrical interference proves excessive, we recommend adding an
insulating transformer and/or using a line filter.
model No.:

81446364-001

After carrying out interference reducing measures, do not bundle the
primary and secondary power supply coils together or insert them in the
same conduit or duct.

Grounding

If grounding the shield wire or other lines proves difficult, ground them separately
to a grounding terminal block.
Type

: A ground resistance of maximum 100Ω

Conductor

: Annealed copper wire, min. 2mm

2

(AWG14)

Max. Length : 20m

Handling Precautions

To ground the

DCP552

, connect the FG terminal (terminal (52) or (53)) to a

single ground point without jumpering.

3

1

E

2

4

Recommended product
81446364-001
Line filter

Other circuits

100 to 240V AC

50/60Hz

200 to 240/200 to 240V
110 to 120/110 to 120V
Insulating transformer

Instrument power supply

Grounding

Grounding

DCP552

GND

53

or

39

40

52

Chapter 4. WIRING

Ground with a ground resistance

of maximum 100½

,+2##

or

53

Grounding terminal block

FG terminals

52

Shield