Event Output (Open Collector Output) Connection

Handling Precautions

• Do not short-circuit the positive (+) terminal of the external power supply

to terminals (5) to (8), (17) to (20), (10), (11), (22), (23), (27), (28), (31),
and (32) on the

DCP552

. Doing so causes the open collector outputs to

malfunction. (There is no short-circuit preventing circuit inside.)

• When connecting a semiconductor load such as a programmable

controller (sequencer), select a module in which the current directions
match.
Use one made inoperative by the leakage current produced when the
digital outputs are shut off.

4-11

5

+

6

7

8

17 18 19 20

9

EV1 EV2 EV3 EV4 EV5 EV6 EV7 EV8

External power supply
12 to 24V DC

Max. load current
Max. common current
Leakage current when OFF

External power supply
12 to 24V DC

Max. load current
Max. common current
Leakage current when OFF

10

+

11 22 23 27 28 31 32 24

EV9 EV10 EV11 EV12 EV13 EV14 EV15 EV16

Load

Load

Load

Load

Load

Load

Load

Load

Load

Load

Load

Load

Load

Load

Load

Load

: 70mA/point
: 500mA
: less than 0.1mA

: 70mA/point
: 500mA
: less than 0.1mA