4-15

3-wire system RS-485 connection diagram

Attach 1/2W or greater terminating resistances of 150Ω ±5% at each end of the
communications lines. Ground the shield FGs at one end in one location, not at
both ends.
When only three RS-485 terminals are provided, the areas designated with an
asterisk (*) are connected internally.

SDA

SDB

RDA

RDB

SG

SDA

Shield

SDB

RDA

RDB

SG

Shield

Shield

Master station

*

Terminating resistor

Terminating resistor

Slave station side

DCP552

SDA

SDB

RDA

RDB

SG

RDA

RDB

SDA

SDB

SG

FG

Slave station side

DCP552

Slave station side

DCP552

*

60

61

62

63

64

FG

60

61

62

63

64

FG

60

61

62

63

64

FG

Chapter 4. WIRING