Honeywell DCP552 Mark II User Manual

Page 49

Advertising
background image

5-3

RAMP-T system (θ setting)

In the RAMP-T system, a segment is set using SP and ramp θ (theta).
SP setting

: within the upper and lower SP limiter range

θ setting

: 1 to 10000 (SPU/hour, SPU/min, SPU/sec)

(Time units are selected using the

C62

setup data setting.)

SP is a point on the elapsed time axis in the current segment which is an extended
straight line, the ramp set value of the current segment when the SP set value in
the previous segment is the start point.
The end point is the point where this line reaches the SP setpoint of the current
segment. Note that the RAMP-T system cannot be used in the first segment.
SP calculation: SP = θ set value × segment elapsed time + previous segment SP.

RAMP-E system (∆ SP setting)

In the RAMP-E system, segments are set using SP and ∆ SP (digital SP) for each
external switch input pulse.
SP setting : within the upper and lower SP limiter range
∆ SP setting: 1 to 10000 SPU
The start point is the SP set value in the previous segment.
SP is a value resulting from adding a multiple of the external switch input count to
the SP set value when the SP in the previous segment is the start point.
The segment ends when this SP reaches the SP setting in the current segment and
the current segment SP is more than the previous segment SP or when current
segment SP is less than the previous segment SP.
SP calculation: when current segment SP is more than the previous segment SP,
SP = ∆ SP set value × external switch input count + the previous segment SP.
When current segment SP is less than the previous segment SP,
SP = – (∆ SP set value × exernal switch input count) + the previous segment SP.

Chapter 5. FUNCTIONS

SP setting of
current segment

SP of previous
segment

Unit time
(Set unit time using setup data

C62

.)

setting

SP

Time

θ

Current segment SP setting

SP of previous
segment

∆ SP setting

∆ SP setting

External switch input (1)
(Set external switch input using one of setups

C71

to

C74

.

)

SP

Time

(2)

Advertising