5-4

NOTE

•Select the program pattern setting system using setup data setting

C61

.

0: combined use of RAMP-X and RAMP-T
1: combined use of RAMP-X and RAMP-E

•Select time setting units using setup data setting

C62

.

0: hours and minutes
1: minutes and seconds
2: 0.1 seconds

•Select θ setting units using setup data setting

C62

.

0: SPU/hour
1: SPU/min
2: SPU/sec

•Select SP setting and SP setting decimal position using setup data setting

C65

.

0: XXXXX
1: XXXX.X
2: XXX.XX
3: XX.XXX
4: X.XXXX

•External switch for pulse input requires 1: RAMP-E using a setup data setting

between

C71

to

C74

.

•The pulse input interval time can be checked by setting event type 93 in the event.

Event type 93 is RAMP-E time monitored during a period of 0.0 to 3000.0
seconds.
Even when a setting is exceeded and there is no pulse input, the event remains on.

Chapter 5. FUNCTIONS