Honeywell DCP552 Mark II User Manual

Page 55

Advertising
background image

5-9

• Event on delay

The number of the event to be delayed and the delay time can be set regardless
of event type. The delay turns on the output for the duration of the delay when
the event meets the conditions for going from OFF to ON. When this function
is combined with the event standby function, the event on delay operates when
the standby state is cleared.

• Segment event progress

•The output stays OFF until the program reaches a segment with an event.
•The event goes ON or OFF according to the set value of the event.
•Previous settings are valid until segments with other event settings are reached.
•Previous settings are valid when the program has reached segment number 1

using the cycle function or pattern link function. The output is turned off if
there is no event in segment number 1.

• Other functions

Normal PV1 upper and lower limit operation event and normal PV2 upper and
lower limit operation events operate in the READY mode.

Chapter 5. FUNCTIONS

PV upper limit
Normal PV1 upper limit operation
Normal PV2 upper limit operation

H

EV

PV

PV lower limit
Normal PV1 lower limit operation
Normal PV2 lower limit operation

H

EV

PV

Deviation upper limit
Deviation upper limit with standby

H

SP+EV

PV

Deviation lower limit
Deviation lower limit with standby

H

SP+EV

PV

Absolute value deviation upper limit
Absolute value deviation upper limit with standby
SOAK absolute value deviation upper limit*
SOAK absolute value deviation upper limit with standby*

H

SP

PV

H

EV

EV

Absolute value deviation lower limit
Absolute value deviation lower limit with standby
SOAK absolute value deviation lower limit*
SOAK absolute value deviation lower limit with standby*

H

SP

PV

H

EV

EV

Items marked * operate only in SOAK segments.

Items marked * operate only in SOAK segments.

Advertising