5-13

•Timed code event

This function is a combination of a code event and a time event. The set code
value is output at the set time. The number of settings that can be made in the first
segment is the same as the number of output points. For example, for a 3-point
output up to three settings can be made in the first segment.
Like a time eventit, a setting within the segment period is valid and those that
exceed it are ignored. When the program reaches the start time of the first
segment or a new segment, the set code value is 0 (all points off) until the set time
of the time event.

Chapter 5. FUNCTIONS

Segment

Set value

Code value
1 in event 3

Code value
2 in event 4

Code value
4 in event 5

Output code

1

2

5

4

3

Not set

5

3

Not set

6

0

OFF

ON ON

OFF OFF OFF

OFF

OFF

OFF

ON

OFF

0
OFF,OFF,OFF
0, 0, 0

5
*1

3
OFF,OFF,OFF
0, 0, 0

0
*3

0
OFF,OFF,OFF
0 , 0, 0

Set time

Not set

0.00 0.10

Not set

0.30

0.00

Time

0.10

0.30

OFF

OFF OFF

ON

ON

OFF OFF OFF

ON

3
*2

6
*4

Example: Setting a timed code with 3 output points in event 3

*1: ON,OFF,ON

1, 0, 1

*2: OFF,ON,ON

0, 1, 1

*3: OFF,OFF,OFF

0, 0, 0

*4: ON,ON,OFF

1, 1, 0

The table below shows the output state when a value of 5 is set in segment 2 and set to start at the
beginning of the segment, a value of 3 is set to occur 0:10 after the start of segment 2 and a value
of 4 is set to occur 0:30 after the start of segment 4.