Pid group selection, Selection of ouput limiter group – Honeywell DCP552 Mark II User Manual

Page 62

Advertising
background image

5-16

PID group selection

•Separate PID group selections can be set in CH1 and CH2 programs.

•PID groups can be selected in two ways: by setting a PID segment or through

automatic PID group switching.
A PID group segment and automatic PID group switching can also be combined.
When a PID group number is set to 0, the setting in the previous segment is
continued.

•In a PID group segment setting a PID group number is set in each segment and

PID parameters are used for calculating the control output. The nine PID groups

PID1

to

PID9

can be used.

•In automatic PID group switching, the entire SP scale is divided into seven zones

assigning

CP-A1

to

CP-A6

to each. The PID constants that are used according to

SP values are automatically selected to calculate control output. The PID group
number for each segment specifies A. Seven PID groups from

PID-A1

to

PID-A7

can be used.

Selection of ouput limiter group

•Separate output limiter groups can be set in CH1 and CH2 programs.

•Output limiter group number can be set for each segment to control the lower

limit (OL) and upper limit (OH) of the control output.

oL

and

oH

groups 1 to 9

can be used.

•The output limiter can only be specified by segment; automatic selection cannot

be made.

•When the output limiter is set to 0, the setting in the previous segment is

continued.

Chapter 5. FUNCTIONS

PID group number

1

2

3

4

PID group segment setting

SP

Time

Zone 7

Zone 6

Zone 5

Zone 4

Zone 3

Zone 2

Zone 1

Entire SP range is
divided into seven zones.

CP-A6

CP-A5

CP-A4

CP-A3

CP-A2

CP-A1

SP