5-18

• G.SOAK at end of segment

PV and SP are compared at the end of the segment. The operation in that
segment ends when the absolute value continues beyond the G.SOAK time and
becomes narrower than G.SOAK width.
A G.SOAK wait state continues until these conditions are met which is
announced by the flashing of the linear LED at the center of the profile display.
The operating condition is the same as HOLD at the end of a segment (time =
set segment time).

• G.SOAK for entire segment

PV and SP are compared at across the entire segment. The operation in that
segment continues when the absolute value continues beyond the G.SOAK time
and becomes narrower than G.SOAK width.
A G.SOAK wait state continues until these conditions are met which is
announced by the flashing of the linear LED at the left and the center of the
profile display.
The operating condition is the same as HOLD at the continued time.

PV shift

Separate PV shift settings can be made in CH1 and CH2 programs.
A PV correction value can be set for each segment. PV is PV input value plus PV
bias and PV shift. Note, however, that in the READY mode and the constant value
control mode, PV bias but not PV shift is added to the PV input value.
The setting in the previous segment continues when PV shift is set to “-----”
(nothing).

Chapter 5. FUNCTIONS

G. SOAK
width

G. SOAK
width

SP

PV

Segment

setting time

G.SOAK wait time

Time

SP

Segment number

1

2

3

4

5

6

Nothing Nothing

+5ûC

Nothing +10ûC 0ûC

PV shift setting

+5ûC

+10ûC

Time

SP

PV

PV input value

+5ûC setting is continued.

A ÒNo PV shift settingÓ that continues from the first

segment has the same effect as a PV shift 0¡C setting.