4 external switch operation, 6 - 4 external switch operation, External switch input – Honeywell DCP552 Mark II User Manual

Page 94

Advertising
background image

6-12

Chapter 6. OPERATION

6 - 4

External Switch Operation

External switch input

A total of 16 external switch inputs are available. Each input is called SW1, SW2,

etc. up to SW16. (SW: external switch input)

Types of external switch inputs

SW1 to 4 and SW9 to 16 are tied.

SW5 to 8 functions are selected using setup data settings

C71

to

C74

.

SW9 to 14 are for program selections. Selections are made by entering BCD code

or binary codes in the setup data

C75

. When two weights are given for an item,

the right weight is for binary figures and the left is for BCD.

NOTE

• When G.SOAK is cleared using an OR condition and an external switch is on,

or PV enters the G.SOAK width, a G.SOAK wait is cleared.

• When G.SOAK is cleared using an AND condition and an external switch is on

and PV enters the G.SOAK width, a G.SOAK wait is cleared.

External

switch number

Function

Detection way

SW1

RUN

Leading edge

SW2

HOLD

Leading edge

SW3

RESET

Leading edge

SW4

ADV

Leading edge

SW5

Selects one of the following functions using setup settings.

SW6

RAMP-E

Leading edge

SW7

FAST

Leading edge

SW8

Clears G.SOAK using the OR condition.

Status

Clears G.SOAK using the AND condition.

Status

MANUAL/AUTO

Leading/trailing edge

AT start/stop

Leading/trailing edge

AUTO Loading

Leading edge

O

2

sensor check

Leading edge

SW9

Selects program number, weight 1

Status

SW10

Selects program number, weight 2

Status

SW11

Selects program number, weight 4

Status

SW12

Selects program number, weight 8

Status

SW13

Selects program number, weight 10 or 16

Status

SW14

Selects program number, weight 20 or 32

Status

SW15

CH1 operation canceled

Status

SW16

CH2 operation canceled

Status