6-13

Chapter 6. OPERATION

• The on and off states of SW15 and SW16 determine whether external SW1 to

SW14 operations are enabled or disabled. Note, however, that the autoload

function and the O

2

sensor check function cannot be disabled by SW15 and

SW16.

Selecting programs

• Programs can be selected using the external switches in the READY program

run mode.

• Programs are selected using the external switches and the BCD system or the

binary system, and are set in setup data

C75

. In the BCD system, four switches

SW9 to 12 are used to set the one digit and the two switches SW13 to 14 are

used to set the ten digit. In the binary system, six switches SW9 to 14 are used

to set. Settings made with these systems are shown in the tables below.

BCD system

Status

BCD system (the ten digit)

External switch number

Weight

SW13

10

SW14

20

Number selection

OFF ON OFF ON
OFF OFF ON ON

0

10

20

30

Status

BCD system (the one digit)

External switch number

Weight

SW9

1

SW10

2

SW11

4

SW128

Number selection

OFF ON OFF ON OFF ON OFF ON OFF ON
OFF OFF ON ON OFF OFF ON ON OFF OFF
OFF OFF OFF OFF ON ON ON ON OFF OFF
OFF OFF OFF OFF OFF OFF OFF OFF ON ON

0

1

2

3

4

5

6

7

8

9

SW15

OFF
ON
OFF
ON

SW16

OFF
OFF
ON
ON

Enabled in both CH1 and CH2
Enabled in CH2, but disabled in CH1
Enabled in CH1, but disabled in CH2
Disabled in both CH1 and CH2

External switch operation