Appendix B:

De-rating for High Altitude

For U.S. installations, the Clarity Fireplace Insert

is approved for elevations up to 2000 feet using the
factory-installed burner injectors. At elevations
above 2000 feet, U.S. codes require a decrease in
the input rating by changing the burner injectors to
a smaller size. The chart below lists by part num-
bers the appropriate injectors for both LP and natu-
ral gas at various altitudes.

For Canadian installations, the Clarity Fireplace

Insert is approved for elevations up to 1370 meters
(4500 feet).

For high altitude installations above 1370 meters (4500

feet), consult the local gas distributor or the authority
having jurisdiction for proper rating methods.

NOTE: The difference in altitude derating require-

ments for the U.S. and Canada is simply a result of dif-
ferences in testing standards between the two coun-
tries.

If the installer must convert the unit to adjust for vary-

ing altitudes, an information sticker like the one below
must be filled out and affixed to the appliance at the
time of conversion.

THE CONVERSION SHALL BE CARRIED OUT

BY A MANUFACTURER'S AUTHORIZED REP-
RESENTATIVE IN ACCORDANCE WITH THE
REQUIREMENTS OF THE MANUFACTURER,
PROVINCIAL OR TERRITORIAL AUTHORI-
TIES HAVING JURISDICTION AND IN AC-
CORDANCE WITH THE CURRENT EDITION
OF THE REQUIREMENTS OF THE CAN/CGA-
B141.1 OR CAN/CGA-B141.2 INSTALLATION
CODES.

LA CONVERSION DOIT ETRE EFFECTUÉE
CONFORMÉMENT AUX RÉGLEMENTATION
PROVINCIAUX EN CAUSE ET AUX
EXIGENCES DES CODES D'INSTALLATION
CAN/CGA-B149.

NATURAL GAS

Front

Harman

Center

Harman

Rear

Harman

Nominal Btu

Altitude

Injector Part No.

Injector Part No.

Injector Part No.

Input Rate

0-2000'

47

Standard

56

Standard

44

Standard

40,000

2000-3000'

47

3-40-25848

56

Standard

45

3-40-25840

38,400

3000-4000'

48

3-40-25849

56

Standard

45

3-40-25841

36,900

4000-5000'

49

3-40-25849

56

3-40-25857

46

3-40-25842

35,400

5000-6000'

49

3-40-25850

57

3-40-25857

47

3-40-25842

34,000

6000-7000'

50

3-40-25850

57

3-40-25857

47

3-40-25843

32,600

7000-8000'

50

3-40-25851

58

3-40-25858

48

3-40-25843

31,300

8000-9000'

51

3-40-25851

58

3-40-25858

48

3-40-25844

30,100

PROPANE

Front

Harman

Center

Harman

Rear

Harman

Nominal Btu

Altitude

Injector Part No.

Injector Part No.

Injector Part No.

Input Rate

0-2000'

57

Standard

71

Standard

55

Standard

40,000

2000-3000'

59

Standard

71

Standard

55

3-40-25854

36,900

3000-4000'

57

Standard

71

Standard

56

3-40-25854

36,900

4000-5000'

58

3-40-25857

71

Standard

56

3-40-25854

35,400

5000-6000'

59

3-40-25857

71

Standard

56

3-40-25855

32,600

6000-7000'

59

3-40-25857

71

Standard

57

3-40-25855

32,600

7000-8000'

60

3-40-25858

71

Standard

57

3-40-25856

30,100

8000-9000'

61

3-40-25858

71

Standard

58

3-40-25856

30,100