Specifications
I/O Module Configuration

96

UMC800 Controller Installation and User Guide

Release F

4/01

Component

Parameter

Description

Pulse/Frequency Inputs
with Digital Outputs

Input 1 to 4
Voltage Levels

Logic Input High Vih:

3.0 Vdc

Logic Input Low Vil:

1.0 Vdc

Absolute Max:

27 Vdc

Absolute Min:

0.0 Vdc

Digital Output
(Open Collector
Circuit)

Max On DC Impedance: 330 ohms
Min Off DC Impedance:

>10 Mohms

Max Source Voltage:

27 Vdc

Min Load DC Impedance: 0 ohms

Frequency Mode
Limitations

Frequency Min:

10 Hz frequency mode

Frequency Max:

100 kHz frequency mode

Min Frequency Duty Cycle @ 100 kHz:

10 %

Max Frequency Duty Cycle @ 100 kHz:

90 %

Pulse Mode Limitations

Pulse Width Min:

100 uSec

Pulse Width Max:

unlimited

Outputs per Module

6

Relay (Alarm) Outputs

(Module ID 6)

Contact Rating

4 A, 250 Vac on resistive load

Contact Type

SPST normally closed (NC), individually configurable to
normally open (NO) via jumper

Time Resolution

4 msec.

Module

Any Digital Output may be configured.

Time Proportional
Outputs (TPO)

Synchronization

Individual TPOs are not synchronized with others.

*Base Power Required is the power required to provided module operation within specifications.