Specifications

PV Inputs

Release F

UMC800 Controller Installation and User Guide

101

4/01

Range

Standard

°F

°C

RTD/Ohms

Pt 100 at 0 °C

–130

to

464

–58

to

302

32

to

212**

32

to

392

32

to

752

–328

to

1472

–90

to

240

–50

to

150

0

to

100**

0

to

200

0

to

400

–200

to

800

IEC 751-1986
IEC 751-1986
IEC 751-1986
IEC 751-1986
IEC 751-1986
IEC 751-1986

Ni 50 ohms

–112

to

608

–80

to

320

Edison #2045A-1962

Ni 508 ohms

–112

to

302

–80

to

150

Cu 10 ohms

–4

to

482**

–20

to

250**

General Electric

Ohms

0

to

200 ohms

0

to

2000 ohms

JIS

–58

to

302

32

to

212**

32

to

392

32

to

752

–328

to

932

–50

to

150

0

to

100**

0

to

200

0

to

400

–200

to

500

JIS C 1604-1981
JIS C 1604-1981
JIS C 1604-1981
JIS C 1604-1981
JIS C 1604-1981

Linear

Milliamperes

0

to

20 mA*

4

to

20 mA*

Millivolts

0

to

10 mV

–10

to

10 mV

0

to

20 mV

–20

to

20 mV

0

to

50 mV

–50

to

50 mV

10

to

50 mV

0

to

100 mV

–100

to

100 mV

0

to

500 mV

–500

to

500 mV

Volts

0

to

1 V

–1

to

1 V

0

to

2 V

–2

to

2 V

0

to

5 V

–5

to

5 V

1

to

5 V

0

to

10 V

–10

to

10 V

Carbon
Oxygen

0

to

1250 mV

–30

to

510 mV

*mA inputs must be connected with a 250 ohm resistor across the input terminals.

**These ranges have an accuracy of 0.25 %.