Honeywell UMC800 User Manual

Page 32

Advertising
background image

Mounting and Wiring
Signal Wiring

24

UMC800 Controller Installation and User Guide

Release F

4/01

Analog input / analog output field wiring

Shielded twisted pairs are recommended (and required for CE approval) for analog input (AI) and analog
output (AO) module field wiring. If a cabinet shield termination point is not available, the optional shield
termination bracket may be used, (specify part number 51309814-501). The shield termination point is a
bracket attached at the top and/or bottom on the front of the controller enclosure. The wiring shields are
attached using the screws of the shield termination. Figure 12 shows the field wiring termination strip
attached to the bottom front of the enclosure.

Figure 12 Field wiring shield termination

Advertising