Honeywell UMC800 User Manual

Page 35

Advertising
background image

Mounting and Wiring

Signal Wiring

Release F

UMC800 Controller Installation and User Guide

27

4/01

Analog outputs (module ID 2)

The Analog Output (AO) module provides four outputs at 0 mA to 20 mA (configurable for 4 mA to
20 mA or any span between 0 mA to 20 mA). When not used for an analog output, an output channel may
be used to power a transmitter with 24 Vdc power. The controller will support up to 4 AO modules, for a
total of 16 outputs. Figure 15 shows the terminal connections for the AO module. See Specifications
section for details on all I/O module specifications.

Gnd

4 to 20 ma
Generator

+

-

4 to 20 mA Output

Ground Terminal

Load

Field Wiring

+

-

24 V

DC

Power

Gnd

Field Wiring

12

11

10

9

8

7

6

5

4

3

2

1

2

Channel 4

Channel 3

Channel 2

Channel 1

ATTENTION

Channels not used as analog outputs can be used to supply a transmitter with 24 Vdc power.

Figure 15 AO module terminal block connections

Advertising