Honeywell UMC800 User Manual

Page 38

Advertising
background image

Mounting and Wiring
Signal Wiring

30

UMC800 Controller Installation and User Guide

Release F

4/01

Digital outputs

There are four types of Digital Output (DO) modules that provide three types of Off/On control.

1.

Relay (alarm) output

(Module ID 6) 46190308-503

2.

DC output

(Module ID 7) 46190341-501

3.

AC output

(Module ID 8) 46190344-501

4.

AC high output

(Module ID A) 46190344-502

Figure 17 shows the terminal block connections for the DC output and AC output DO modules. See
Specifications section for details on all I/O module specifications.

+

24V

-

Load

Field Wiring

Fuse

Module ID #7
DC IOutput (24 Vdc)

12

11

10

9

8

7

6

5

4

3

2

1

DO 6

DO 4

DO 3

DO 1

DO 5

DO 2

Module ID
#6, 7, 8,
or A

Field Wiring

L1

L2

Load

Module ID #6
Relay (Alarm) Output

VCC

L1

L2

Load

Fuse

R

Field Wiring

Module ID #8
AC Output (120/240 Vdc)

Module ID A
AC Output (120/240 Vdc)

Wiring same as module 8.

Maximum Load Current:
Outputs

DO 1 – 4 @ .5A
DO 5 and 6 @ 2A

Figure 17 DO module terminal block connections

Advertising