Mounting and Wiring

Signal Wiring

Release F

UMC800 Controller Installation and User Guide

33

4/01

Pulse input/frequency input jumpers

The Pulse/Frequency Input Module with Digital Outputs (Module ID D) contain jumpers to set the de-
energized Input Filter Cutoff Frequency. All four inputs are factory set to 500 KHz as shown in Figure 23.
To change, use needle nose pliers and move the jumper(s) to the desired position. See the figure below for
the default positions and jumper settings for 100 KHz and 5 KHz.

4

6

1

9

0

3

6

0

-5

0

1

OFF

ON

1
2
1

1

2

2

100KHz

5KHz

500KHz

JX1 -

JX2 -

JA1

JA2

JB1

JB2

JC1

JC2

JD2

JD1

Pulse/Frequency Input Board

Figure 20 PI/FI module input filter cutoff frequency setting

Pulse/frequency card wiring

The pulse frequency card input is designed to accept a contact closure type transmitter. The typical wiring
circuit is shown below.

V Supply (DC)

Pulse Transmitter

V Return (DC)

Pulse / Frequency Input Card

Input Connections

R

L

+

-

+

-

R

T=

1k

MOSFET, Open Collector, or
Contact Closure drive.

+

-

Note: All pulse
frequency inputs
share a return
connection that is
common to all pulse /
frequency inputs on a
card.

Figure 21 Pulse/frequency input connections